FOXBORO P0800DY
reloaded. The configuration results and real-time process data are stored in RAM, and ram is installed on the Ethernet network card or battery card
The backup battery can maintain the configuration content and data in case of power failure.
Basic unit pmbo2f characteristics:
mouth
Installation slots of 4 fieldbus interface cards
c
Installation slot of 2 Ethernet network cards
Support redundant operation of Fieldbus interface card
Support hot plug of Fieldbus interface card
Technical indicators of basic unit pib02f:
CPU :Intel 80960HT25/75
32-bit RISC superscalar processor with operation speed of 150 MIPS
4 MB FLASH-EPROM
EEPROM,serial, 16 Kbit
o
Ram 8 MB (with error check and correction function, abb patent)
16 K internal cache (CPU cache RAM)
Ram backup battery (matchdog, optional redundancy)
Equipment internal temperature monitoring
Watchdog
I/0 sweeping cycle: configurable.
Time required to process 1000 IL (instructions):
< 1.0 ms (processing binary and 16 bit arithmetic instructions)
<2ms (processing fixed-point arithmetic instructions)
< 1.5ms (processing 32-bit floating-point arithmetic instructions)
Bthernet network card ei801f/ei802f/ei803f
The industrial Ethernet network card provides communication with the system network diginet s (iee802.3 Ethernet standard)
Interface.
Basic characteristics:
1ee802.3 Ethernet standard
o
Ei801f provides 10base2 thin cable communication interface
Ei802f provides 10BASE5 thick cable connection (through AUI interface)
Ei803f provides 10Base-T twisted pair communication interface
32-bit data bus, 100 mb/s
DMA (direct memory access) mode main memory ram, corresponding CPU operating load <4%
Optional ram backup battery
Fieldbus interface replacement card fi830f/fi820f/fi810f
Fieldbus interface cards are divided into several types according to different protocol standards. Each interface card provides – a fieldbus interface (PROFIBUS,
Can, FF, MODBUS, etc.). The configuration and parameter settings of the interface card itself and the field instrument (or remote i1/0) on the connected fieldbus are still
It is designed by the industrial “unified tool control bui lder without additional software. The interface card can be configured redundantly (separated between each other
Redundant basic unit pm802f) and can be plugged in and out and replaced online.
Fi830f: PROFIBUS DP interface card, as the master station, can connect 126 PROFIBUS DP slave stations, and the communication rate can reach 12mbd
One PS can plug in 4 fieldbus interfaces, connect 496 fieldbus devices, and one city (subsystem) of industrial “system can
Connect 4960 fieldbus devices (10000 i/0).
Fi820f: two serial interfaces are provided to connect the serial protocol equipment. The maximum transmission rate is 38.4kbd and can be configured. Its Standards Association
Modbus Different physical interfaces can be selected for different connection schemes, RS422, RS485, RS232. All interfaces are electrical isolation
Away. And the redundant operation is realized by two redundant field controllers.
Fi8i0f card is a triple can bus protocol interface card (rate 1mbd) used to connect industrial ial “conventional process control station
The i/0 protection unit of the PS is used to receive process signals from the rack mounted i/0 modules supported by the PS. Each field controller PS can only be configured
-Block fi810f card. — The two fi810f interface cards on the redundant PS. can be switched redundantly.
S800 and S900 are distributed i/0 for process control stations. They communicate with their controllers through Prof ibusdp Fieldbus
Communication, which can be installed in the controland PA three levels,