ABB 07AC91
the same field controller PS.
Industrial “field control explosion (AC800F) consists of the following components:
Basic unit pm802f
Power supply sa801f/sd802f
o
Ethernet network card ei801f/ei802f/ei803f
o
Fieldbus interface card fi810f/fi820f/fi830f
Various accessories
The main components of the field controller PS are described below.
Basic unit pm802f
The basic unit pm802f is composed of a metal rack and a CPU motherboard. It periodically scans the data from the
The signals of the field bus sensors are processed according to the control application program configured by the user, and then the calculation results are passed
The fieldbus interface card returns the corresponding fieldbus actuator.
Two field controllers can realize controller 1:1 redundancy, and undisturbed switching between master and slave PS. Two on each PS
Ethernet network card, the second network card is used to connect the system network diginets), and the second network cards can be interconnected with each other to form a special
Redundant communication link (diginetr) to ensure information synchronization between master and slave PS. — However, the master PS fails, and the slave PS can quickly and undisturbed connect the replacement worker
Make. All inputs ccable connection (through AUI interface)
Ei803f provides 10Base-T twisted pair communication interface
32-bit data bus, 100 mb/s
DMA (direct memory access) mode main memory ram, corresponding CPU operating load <4%
Optional ram backup battery
Fieldbus interface replacement card fi830f/fi820f/fi810f
Fieldbus interface cards are divided into several types according to different protocol standards. Each interface card provides – a fieldbus interface (PROFIBUS,
Can, FF, MODBUS, etc.). The configuration and parameter settings of the interface card itself and the field instrument (or remote i1/0) on the connected fieldbus are still
It is designed by the industrial “unified tool control bui lder without additional software. The interface card can be configured redundantly (separated between each other
Redundant basic unit pm802f) and can be plugged in and out and replaced online.
Fi830f: PROFIBUS DP interface card, as the master station, can connect 126 PROFIBUS DP slave stations, and the communication rate can reach 12mbd
One PS can plug in 4 fieldbus interfaces, connect 496 fieldbus devices, and one city (subsystem) of industrial “system can
Connect 4960 fieldbus devices (10000 i/0).
Fi820f: two serial interfaces are provided to connect the serial